Our case study in IAMFA’s Papyrus magazine shows how Wereldmuseum Amsterdam reduced the energy used for collection-storage climate control while improving compliance with its climate requirements.
By Rick Kramer and Joseph Upjohn. Adapted from Papyrus, December 2025, pp. 23–28.
Preserving collections with less energy
Maintaining a single, fixed temperature and relative humidity can require substantial heating, cooling and humidification. Dynamic climate control takes a different approach: it allows smooth, gradual changes within the limits agreed for the collection, using real-time data, building physics and outdoor weather forecasts.
At Wereldmuseum Amsterdam, DYSECO® was integrated with the existing Building Management System (BMS) through an on-site edge device. Shared monitoring dashboards gave conservation and facilities teams visibility into climate performance.
A side-by-side comparison
In September 2025, the museum compared two mechanically identical air-handling units serving adjacent, nearly identical collection-storage zones. AHU 13.2 used standard BMS control; AHU 13.1 combined the BMS with DYSECO’s dynamic control algorithm. The stated climate limits were 18–22°C and 45–55% relative humidity, under ASHRAE Type of Control AA.
The results
- 61% lower electrical energy use: 1,561 kWh with DYSECO compared with 3,960 kWh for the benchmark.
- Improved humidity compliance: 99.9% of the time within the specified limits, compared with 95.8% for the benchmark.
- Temperature within the stated limits 100% of the time in the dynamically controlled zone.
- 47% less time in active conditioning, reducing the operating workload on HVAC components.
Heating full-load hours fell from 400 to 101, and cooling and dehumidification full-load hours from 467 to 171. Humidification increased from 5 to 25 full-load hours, while total electrical energy use still fell substantially.
From fixed setpoints to predictive control
Instead of making scheduled seasonal step changes, DYSECO continuously calculates suitable setpoints within the permitted climate window. This helps avoid unnecessary corrective cycling while respecting the collection’s limits on climate variation.
The results relate to the two units and the September 2025 comparison described in the paper; they are not a whole-building or annual energy-saving figure. The case demonstrates how collection care and energy reduction can support each other.
English PDF · 6 pages · 1 MB · Google Drive
Looking to reduce energy use while caring for your collection?
Contact the DYSECO team to discuss the possibilities for your museum.